Key sequence Indicator Display
example
Explanation
The parameter number is displayed.
Use the Increment or Decrement Key to display “n002.”
Press the Enter Key to display the set value in n002.
Use the Increment or Decrement key to set n002 to 0
unless the value is already set to 0, during which the
display flashes.
Press the Enter Key so that the set value will be entered
and the data display will be lit.
In approximately
1 s.
The parameter number will be displayed again in
approximately 1 s.
H Setting the Rated Motor Current
Parame-
ter
Register Name Description Setting
range
Unit of
setting
Default
setting
Chan-
ges dur-
ing
opera-
tion
n036 0124 Rated
motor
current
Used to set the rated motor
current (A) used for the ref-
erence current of motor
overload detection (OL1).
Note 1. The default set-
ting for the rated
motor current is
the standard rated
current of the
maximum applica-
ble motor.
Note 2. Motor overload
detection (OL1) is
disabled by set-
ting the parameter
to 0.0.
0.0% to
150%
(A) of
rated
output
current
of the
Inverter
0.1 A See note
1 under
“Descrip-
tion.”)
No
Key sequence Indicator Display
example
Explanation
The parameter number is displayed.
Use the Increment or Decrement Key to display “n036.”
Press the Enter Key to display the set value in n036.
Use the Increment or Decrement Key to set n036 to the
rated motor current, during which the display flashes.
Press the Enter Key so that the set value will be entered
and the data display will be lit.
In approximately
1 s.
The parameter number will be displayed again in
approximately 1 s.
Test Run
Chapter 4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3MV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3MV SERIES Specifications

General IconGeneral
ModelSYSDRIVE 3G3MV SERIES
CategoryInverter
Input Frequency50/60 Hz
Output Frequency0.1 to 400 Hz
Cooling MethodForced Air Cooling
Input Voltage200 to 240 VAC, 380 to 480 VAC
Horsepower Range0.1 to 15 HP
Power Range0.1 to 11 kW
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationRS-485
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 65°C
Humidity5 to 95% RH (non-condensing)
Vibration5.9 m/s² or less
Voltage Class200V, 400V