EasyManuals Logo

Omron V1000 User Manual

Omron V1000
411 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #143 background imageLoading...
Page #143 background image
Setting 0: Lower Limit is Determined by d2-02 or Analog Input
The lower frequency reference limit is determined by the higher value of both, parameter d2-02 or an analog input that is
programmed for “Frequency Bias” (H3-02/10 = 0).
Note:
If the external reference change over function (H1- = 2) used to switch between Up/Down function and analog input as reference
source, the analog value would become the lower reference limit when the Up/Down reference is active. Change d4-10 to 1 to make the
Up/Down function independent of the analog input value.
Setting 1: Lower Limit is Determined by Parameter d2-02
Only parameter d2-02 sets the lower frequency reference limit.
n
d4-11: Bi-Directional Output Selection
Selects if the frequency reference or PID output value is converted into bi-directional internal frequency reference. Refer
also to the PID block diagram in Figure 5.18 to see how bi-directional output works.
Note:
When used in combination with PID control, the bi-directional output function can be enabled or disabled using a digital input (H1-
= 7F).
No. Parameter Name Setting Range Default
d4-11 Bi-Directional Output Selection 0 or 1 0
Setting 0: No Conversion
The frequency reference or PID output value is used as it is without being converted. The drive will operate in the direction
selected from 0 to 100% of the maximum output frequency.
Setting 1: Bi-Directional Output Conversion
When the frequency reference or PID output is below 50%, the drive reverses the selected direction. When it is above 50%
the drive works in the selected direction.
n
d4-12: Stop Position Gain
Sets the gain for adjusting the stopping accuracy when simple positioning is selected as the stopping method (b1-03 = 9).
No. Parameter Name Setting Range Default
d4-12 Stop Position Gain 0.50 to 2.55 1.00
Increase the value if the motor stops before the desired stop position is reached. Decrease it if the motor stops too late.
Refer to b1-03: Stopping Method Selection on page 105 for details on simple positioning.
u
d7: Offset Frequencies
n
d7-01 to d7-03: Offset Frequency 1 to 3
Three different offset values can be added to the frequency reference. They can be selected using digital inputs programmed
for Offset frequency 1, 2 and 3 (H1- = 44, 45, 46). The selected offset values are added if two or all three inputs are
closed at the same time.
Note:
This function can be used to replace the “Trim Control” function (H1- = 1C/1D) of earlier OYMC drives.
No. Parameter Name Setting Range Default
d7-01 Offset Frequency 1 -100.0 to 100.0% 0%
d7-02 Offset Frequency 2 -100.0 to 100.0% 0%
d7-03 Offset Frequency 3 -100.0 to 100.0% 0%
Figure 5.39 illustrates the Offset Frequency Function.
5.4
d: Reference Settings
142
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23

Table of Contents

Other manuals for Omron V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron V1000 and is the answer not in the manual?

Omron V1000 Specifications

General IconGeneral
Cooling MethodFan cooling
Enclosure RatingIP20
CommunicationModbus RTU
Output Power0.4-15kW
Output Frequency Range0 to 400 Hz
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
Supply Voltage200-240V AC (3-phase)

Related product manuals