E2-11: Motor Rated Power
This parameter sets the motor rated power in kW. During Auto-Tuning the value must entered to parameter T1-02. If Auto-
Tuning completes successfully, the value entered will automatically be saved to E2-11.
No. Parameter Name Setting Range Default
E2-11 Motor Rated Power 0.00 to 650.00 kW
Depending on
o2-04
n
E2-12: Motor Iron-Core Saturation Coefficient 3
This parameter sets the motor iron saturation coefficient at 130% of the magnetic flux.
No. Parameter Name Setting Range Default
E2-12 Motor Iron-Core Saturation Coefficient 3 1.30 to 5.00 1.30
u
E3: V/f Characteristics for Motor 2
These parameters set the V/f pattern used for motor 2. Refer to Setting 16: Motor 2 Selection on page 164 for details on
switching motors.
n
E3-01: Motor 2 Control Mode Selection
Selects the control mode for motor 2. Motor 2 can not be used with OLV for PM.
No. Parameter Name Setting Range Default
E3-01 Motor 2 Control Mode Selection 0 or 2 0
Setting 0: V/f Control
Setting 2: Open Loop Vector Control
n
E3-04 to E3-13
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 like shown in Figure 5.41.
No. Parameter Name Setting Range Default
E3-04 Motor 2 Max Output Frequency 40.0 to 400.0 Hz 50.0 Hz
E3-05 Motor 2 Max Voltage
0.0 to 255.0
<1>
200.0 V
<1>
E3-06 Motor 2 Base Frequency 0.0 to 400.0 50.0 Hz
E3-07 Motor 2 Mid Output Frequency 0.0 to 400.0
<2>
E3-08 Motor 2 Mid Output Frequency Voltage
0.0 to 255.0
<1> <2>
E3-09 Motor 2 Minimum Output Frequency 0.0 to 400.0
<2>
E3-10 Motor 2 Minimum Output Frequency Voltage
0.0 to 255.0
<1> <2>
E3-11 Motor 2 Mid Output Frequency 2 0.0 to 400.0 0.0 Hz
E3-12 Motor 2 Mid Output Frequency Voltage 2
0.0 to 255.0
<1>
0.0 Vac
E3-13 Motor 2 Base Voltage
0.0 to 255.0
<1>
0.0 Vac
<1> Values shown here are for 200 V class drives. Multiply voltage values by 1.15 for U-spec drives. Double the value when using a 400 V class
drive.
<2> Default setting is determined by the control mode for motor 2.
5.5
E: Motor Parameters
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
149
5
Parameter Details
7/16/2008-13:23

Table of Contents

Other manuals for Omron V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron V1000 and is the answer not in the manual?

Omron V1000 Specifications

General IconGeneral
Cooling MethodFan cooling
Enclosure RatingIP20
CommunicationModbus RTU
Output Power0.4-15kW
Output Frequency Range0 to 400 Hz
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
Supply Voltage200-240V AC (3-phase)