2.1 Section Safety
WARNING
Fire Hazard
Provide sufficient cooling when installing the drive inside an enclosed panel or cabinet.
Failure to comply could result in overheating and fire.
When multiple drives are placed inside the same enclosure panel, install proper cooling to ensure air entering the enclosure
does not exceed 40 °C.
CAUTION
Crush Hazard
Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main body of the drive falling.
NOTICE
Observe proper electrostatic discharge (ESD) procedures when handling the drive.
Failure to comply could result in ESD damage to the drive circuitry.
It may be difficult to perform maintenance on the cooling fans of drives installed in a vertical row inside an
enclosure.
Ensure adequate spacing at the top of the drive to perform cooling fan replacement when required.
Operating the motor in the low-speed range diminishes the cooling effects, increases motor temperature, and may
lead to motor damage by overheating.
Reduce the motor torque in the low-speed range whenever using a standard blower cooled motor. If 100% torque is
required continuously at low speed, consider using a special drive or vector motor. Select a motor that is compatible with
the required load torque and operating speed range.
Do not operate motors above the maximum rated RPM.
Failure to comply may lead to bearing or other mechanical motor failures.
The speed range for continuous operation differs according to the lubrication method and motor manufacturer.
If the motor is to be operated at a speed higher than the rated speed, consult with the manufacturer.
Continuously operating an oil-lubricated motor in the low-speed range may result in burning.
2.1 Section Safety
28
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:22

Table of Contents

Other manuals for Omron V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron V1000 and is the answer not in the manual?

Omron V1000 Specifications

General IconGeneral
Cooling MethodFan cooling
Enclosure RatingIP20
CommunicationModbus RTU
Output Power0.4-15kW
Output Frequency Range0 to 400 Hz
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
Supply Voltage200-240V AC (3-phase)

Related product manuals