F6-14: BUS Error Auto Reset
Selects if a BUS error can be automatically reset if automatic fault retry is enabled.
No. Parameter Name Setting Range Default
F6-14 BUS Error Auto Reset 0 or 1 0
Setting 0: Disabled, Auto Reset Not Possible
Setting 1: Enabled, Auto Reset Possible
n
F6-30: PROFIBUS Node Address
Sets the node address of a PROFIBUS-DP option card.
No. Parameter Name Setting Range Default
F6-30 PROFIBUS Node Address 0 to 125 0
n
F6-31: PROFIBUS Clear Mode Selection
Determines the operation when a “Clear Mode” command is received.
No. Parameter Name Setting Range Default
F6-31 PROFIBUS Clear Mode Selection 0 or 1 0
Setting 0: Reset
Resets the drive operation (frequency reference, inputs, outputs etc.).
Setting 1: Maintain the Previous State
Returns the drive status to what it was prior to receiving the Clear Mode command.
n
F6-32: PROFIBUS Data Format Selection
Selects the data format used for PROFIBUS communication.
No. Parameter Name Setting Range Default
F6-32 PROFIBUS Data Format Selection 0 or 1 0
Setting 0: PPO Type Data Format
Setting 1: Conventional Data Format
n
F6-35: CANopen Node ID Selection
Selects the node ID of a CANopen option board.
No. Parameter Name Setting Range Default
F6-35 CANopen Node ID Selection 0 to 127 99
n
F6-36: CANopen Communication Speed
Sets the communication speed for a CANopen option card.
No.
Parameter Name Setting Range Default
F6-36 CANopen Communication Speed 0 to 8 6
Settings:
F6-36 Communication Speed F6-36 Communication Speed
0 Auto detection 5 250 kbps
1 10 kbps 6 500 kbps
2 20 kbps 7 800 kbps
3 50 kbps 8 1 Mbps
4 125 kbps
n
F6-40: CompoNet Node ID
Selects the node ID of a CompoNet option board.
No. Parameter Name Setting Range Default
F6-40 CompoNet Node ID 0 to 63 0
5.6 F: Option Settings
156
SIEP C710606 20 OYMC AC Drive - V1000 User Manual