No. Parameter Name Setting Range Default
F6-58
<1>
DeviceNet Torque Scaling -15 to 15 0
F6-59
<1>
DeviceNet Power Scaling -15 to 15 0
F6-60
<1>
DeviceNet Voltage Scaling -15 to 15 0
F6-61
<1>
DeviceNet Time Scaling -15 to 15 0
<1> Valid from drive software version 1011 and later.
Setting
The monitor value in the AC/DC Drive Object 2AH is calculated by:
AC/DC Drive Object 2AH Monitor = Drive Value x 2
Scaling
Example:
If the drive output frequency monitor (U1-02) is 50.0 and the scaling is set to F6-56 = 6, then the value in the AC/DC
Drive Object 2AH, Instance 1, Attribute 7 would be 500 x 2
6
= 32000.
n
F6-62: DeviceNet Heartbeat Interval
Sets the heartbeat interval for DeviceNet communications. A setting of 0 disables the Heartbeat function.
No. Parameter Name Setting Range Default
F6-62
<1>
DeviceNet Heartbeat 0 to 10 0
<1> Valid from drive software version 1011 and later.
n
F7-01 to F7-04: Ethernet IP Address 1 to 4
The combination of these parameters sets the IP address of an Ethernet option board if installed. The address is set like
F7-01.F7-02.F7-03.F7-04. The default address is 192.168.1.20.
No. Parameter Name Setting Range Default
F7-01 Ethernet IP Address 1 0 to 255
192
<1>
F7-02 Ethernet IP Address 2 0 to 255
168
<1>
F7-03 Ethernet IP Address 3 0 to 255
1
<1>
F7-04 Ethernet IP Address 4 0 to 255
20
<1>
<1> Valid from drive software version 1011 and later.
n
F7-05 to F7-08: Ethernet Subnet Mask 1 to 4
The combination of these parameters sets the Subnet Mask of an Ethernet option board if installed. The mask is set like
F7-05.F7-06.F7-07.F7-08. The default setting is 255.255.255.0.
No. Parameter Name Setting Range Default
F7-05 Subnet Mask 1 0 to 255
255
<1>
F7-06 Subnet Mask 2 0 to 255
255
<1>
F7-07 Subnet Mask 3 0 to 255
255
<1>
F7-08 Subnet Mask 4 0 to 255 0
<1> Valid from drive software version 1011 and later.
n
F7-09 to F7-12: Ethernet Gateway Address 1 to 4
The combination of these parameters sets the gateway address of an Ethernet option board if installed. The address is set
as F7-09.F7-10.F7-11.F7-12. The default address is 192.168.1.1.
No. Parameter Name Setting Range Default
F7-09 Gateway Address 1 0 to 255
192
<1>
F7-10 Gateway Address 2 0 to 255
168
<1>
F7-11 Gateway Address 3 0 to 255
1
<1>
F7-12 Gateway Address 4 0 to 255
1
<1>
<1> Valid from drive software version 1011 and later.
n
F7-13: Ethernet Address Mode at Startup
Determines how the Ethernet option card IP address is set.
No. Parameter Name Setting Range Default
F7-13 Address Mode at Startup 0 to 2 0
5.6 F: Option Settings
158
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23