EasyManuals Logo

Omron V1000 User Manual

Omron V1000
411 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #179 background imageLoading...
Page #179 background image
No. Name Setting Range Default
H3-01 Terminal A1 Signal Level Selection 0 to 1 0
Setting 0: 0 to 10 Vdc with Limit
The input level is 0 to 10 Vdc. Negative input values will be limited to 0.
Example: Terminal A1 is set to supply the frequency reference, and the bias (H3-04) is set to -100%. The frequency
reference can be set from 0 to 100% with an analog input of 5 to 10 V. The frequency reference will be zero when the
analog input is between 0 and 5 V.
0
10 V
100%
-100%
Analog input
voltage
Analog input
value
Negative input is limited to 0
Figure 5.65 Analog Input with Limit (Bias Setting -100%)
Setting 1: 0 to 10 Vdc without Limit
The input level is 0 to 10 Vdc. Negative input values will be accepted.
Example: Terminal A1 is set to supply the frequency reference, and the bias (H3-04) is set to -100%. The frequency
reference can be set from 0 to 100% with an analog input of 5 to 10 V. With an input of 0 to 5 V, the frequency reference
can be set from -100% to 0%. The drive reverses the motor rotation with negative input.
0V
10 V
100%
-100%
Analog input
voltage
Analog input
value
Figure 5.66 Analog Input without Limit (Bias Setting -100%)
n
H3-02: Terminal A1 Function Selection
Determines the function assigned to analog input terminal A1. Refer to Multi-Function Analog Input Terminal
Settings on page 180 for a list of functions and descriptions.
No. Name Setting Range Default
H3-02 Terminal A1 Function Selection 0 to 31 0
Note: If not using an input terminal or if using it in the through-mode, be sure to set that terminal to “F”.
n
H3-03/H3-04: Terminal A1 Gain/Bias Setting
Parameter H3-03 sets the level of the selected input value that is equal to 10 Vdc input at terminal A1 (Gain).
Parameter H3-04 sets the level of the selected input value that is equal to 0 V input at terminal A1.
Both can be used to adjust the analog input A1 characteristics.
No. Name Setting Range Default
H3-03 Terminal A1 Gain Setting -999.9 to 999.9% 100.0%
5.7 H: Terminal Functions
178
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23

Table of Contents

Other manuals for Omron V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron V1000 and is the answer not in the manual?

Omron V1000 Specifications

General IconGeneral
Cooling MethodFan cooling
Enclosure RatingIP20
CommunicationModbus RTU
Output Power0.4-15kW
Output Frequency Range0 to 400 Hz
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
Supply Voltage200-240V AC (3-phase)

Related product manuals