oPE10
V/f Data Setting Error
The following setting errors have occurred where: E1-04 is greater than
or equal to E1-06 is greater than or equal to E1-07 is greater than or equal
to E1-09.
Or the following setting errors have occurred: E3-04 is greater than or
equal to E3-06 is greater than or equal to E3-07 is greater than or equal
to E3-09.
Cause Possible Solutions
Correct the settings for E1-04, -06, -07 and -09 (or E1-04, -06, -07, -09
for motor 2).
LED Operator Display Error Name
oPE11
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
Cause Possible Solutions
The following simultaneous contradictory settings: C6-05 is greater than
6 and C6-04 is greater than C6-03 (carrier frequency lower limit is greater
than the upper limit). If C6-05 is less than or equal to 6, the drive operates
at C6-03.
Correct the parameter settings.
Upper and lower limits between C6-02 and C6-05 contradict each other.
LED Operator Display Error Name
oPE13
Pulse Monitor Selection Error
Incorrect setting of monitor selection for Pulse Train (H6-06).
Cause Possible Solutions
Scaling for the Pulse Train monitor is set to 0 (H6-07 = 0) while H6-06 is
not set to 101, 102, 105, or 116.
Change scaling for the Pulse Train monitor or set H6-06 to 101, 102, 105,
or 116.
LED Operator Display Error Name
oPE14
Application Setting Error
Incorrect setting in combination with simple positioning stop or Bi-
directional output conversion.
Cause Possible Solutions
Parameter b1-03 = 9 (simple positioning stop) and
Drive is not initialized to European settings (o2-09 is not 2)
Dwell function is activated (b6-03 or b6-04 are not 0)
the KEB function is activated (H1- = 65/66/7A/7B)
Stall prevention during deceleration is enabled (L3-04 is not 0)
Overvoltage suppression is enabled (L3-11 = 1)
High slip braking is enabled (H1- = 68)
An S-curve is applied to the deceleration ramp (C2-03 and C2-04 are not
0)
PID output or frequency reference to bi-directional output frequency
reference is enabled (d4-11 = 1) and the drive is not initialized to
European settings.
Check the initialization mode in parameter o2-09. Correct the parameter
settings.
6.6 Operator Programming Errors
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
249