EasyManua.ls Logo

Omron V1000 - 6.8 Diagnosing and Resetting Faults

Omron V1000
411 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LED Operator Display Error Name
Er-05 No-Load Current Error
Cause Possible Solutions
Motor data entered during Auto-Tuning
was incorrect.
Motor data entered to T1 parameters does not match motor nameplate. Enter the correct data.
Restart Auto-Tuning and enter the correct information.
Auto-Tuning did not complete within
designated time frame.
Check and correct faulty motor wiring.
Disconnect the motor from machine and perform Rotational Auto-Tuning.
Drive-calculated values outside parameter
setting range.
LED Operator Display Error Name
Er-08 Rated Slip Error
Cause Possible Solutions
Motor data entered during Auto-Tuning
was incorrect.
Motor data entered to T1 parameters does not match motor nameplate. Enter the correct data.
Restart Auto-Tuning and enter the correct information.
Auto-Tuning did not complete within
designated time frame.
Check and correct faulty motor wiring.
Disconnect the motor from machine and perform Auto-Tuning.
Values calculated by the drive are outside
the allowable parameter setting ranges.
LED Operator Display Error Name
Er-09 Acceleration Error (detected only during Rotational Auto-Tuning)
Cause Possible Solutions
The motor did not accelerate for the
specified acceleration time.
Increase the acceleration time (C1-01).
Check if it is possible to disconnect the machine from the motor.
Torque limit when motoring is too low
(L7-01 and L7-02).
Check the settings of parameters L7-01 and L7-02.
Increase the setting.
LED Operator Display Error Name
Er-11 Motor Speed Fault (detected only when Auto-Tuning is enabled)
Cause Possible Solutions
Torque reference is too high. (Enabled in
OLV only.)
Increase the acceleration time (C1-01).
Disconnect the machine from the motor, if possible.
LED Operator Display Error Name
Er-12 Current Detection Error
Cause Possible Solutions
One of the motor phases is missing (U/T1,
V/T2, W/T3).
Check motor wiring and correct problems.
Current exceeded the current rating of the
drive.
Check the motor wiring for a short between motor lines.
If a magnetic contactor is used between motors, ensure it is on.
Replace the drive.
The current is too low.
Attempted Auto-Tuning without motor
connected to the drive.
Connect the motor and perform Auto-Tuning.
Current detection signal error. Replace the drive.
6.7 Auto-Tuning Fault Detection
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
251
6
Troubleshooting
7/16/2008-13:23

Table of Contents

Other manuals for Omron V1000

Related product manuals