LED Operator Display Error Name
Er-05 No-Load Current Error
Cause Possible Solutions
Motor data entered during Auto-Tuning
was incorrect.
Motor data entered to T1 parameters does not match motor nameplate. Enter the correct data.
Restart Auto-Tuning and enter the correct information.
Auto-Tuning did not complete within
designated time frame.
Check and correct faulty motor wiring.
Disconnect the motor from machine and perform Rotational Auto-Tuning.
Drive-calculated values outside parameter
setting range.
LED Operator Display Error Name
Er-08 Rated Slip Error
Cause Possible Solutions
Motor data entered during Auto-Tuning
was incorrect.
Motor data entered to T1 parameters does not match motor nameplate. Enter the correct data.
Restart Auto-Tuning and enter the correct information.
Auto-Tuning did not complete within
designated time frame.
Check and correct faulty motor wiring.
Disconnect the motor from machine and perform Auto-Tuning.
Values calculated by the drive are outside
the allowable parameter setting ranges.
LED Operator Display Error Name
Er-09 Acceleration Error (detected only during Rotational Auto-Tuning)
Cause Possible Solutions
The motor did not accelerate for the
specified acceleration time.
Increase the acceleration time (C1-01).
Check if it is possible to disconnect the machine from the motor.
Torque limit when motoring is too low
(L7-01 and L7-02).
Check the settings of parameters L7-01 and L7-02.
Increase the setting.
LED Operator Display Error Name
Er-11 Motor Speed Fault (detected only when Auto-Tuning is enabled)
Cause Possible Solutions
Torque reference is too high. (Enabled in
OLV only.)
Increase the acceleration time (C1-01).
Disconnect the machine from the motor, if possible.
LED Operator Display Error Name
Er-12 Current Detection Error
Cause Possible Solutions
One of the motor phases is missing (U/T1,
V/T2, W/T3).
Check motor wiring and correct problems.
Current exceeded the current rating of the
drive.
Check the motor wiring for a short between motor lines.
If a magnetic contactor is used between motors, ensure it is on.
Replace the drive.
The current is too low.
Attempted Auto-Tuning without motor
connected to the drive.
Connect the motor and perform Auto-Tuning.
Current detection signal error. Replace the drive.
6.7 Auto-Tuning Fault Detection
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
251
6
Troubleshooting
7/16/2008-13:23

Table of Contents

Other manuals for Omron V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron V1000 and is the answer not in the manual?

Omron V1000 Specifications

General IconGeneral
Cooling MethodFan cooling
Enclosure RatingIP20
CommunicationModbus RTU
Output Power0.4-15kW
Output Frequency Range0 to 400 Hz
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
Supply Voltage200-240V AC (3-phase)