Programming
88 900-0117-01-00 Rev B
Gen Alert
can be used as a limited functionality controller for an AC generator with a remote start feature. It can
start and stop the generator based on DC (battery) voltage levels.
This option has settable DC voltage and time parameters.
Note: This option does not have the same advantages as the Advanced Generator Start (AGS) function
which is controlled directly by the MATE3. (See page
35105.)
Figure 100 Gen Alert
Fault
enables the AUX output when the inverter shuts down due to an error condition (see page
35
43). It can
activate a light or alarm to show that the inverter has failed. This menu has no adjustable settings.
Vent Fan
enables the AUX output in response to high DC (battery) voltage. It can run a small fan to ventilate
the battery compartment to eliminate gases that result from battery charging.
This option has settable DC voltage and time parameters.
Figure 101 Vent Fan
Cool Fan
enables the AUX output when the inverter reaches a high internal temperature. It is intended to
trigger a small external fan for additional cooling. This includes sealed inverter models which come with a Turbo
fan.
This menu has no adjustable settings.
Divert DC
enables the AUX output to divert excess energy to a DC load, in response to high DC (battery)
voltage. The AUX output controls a larger relay, which allows current to flow to a dedicated DC load when
energized.
This option has settable DC voltage and time parameters.
Figure 102 Divert DC
Set Points for
Divert DC:
Enable Voltage
– Sets the high-voltage level at which the
Divert DC
function turns on the AUX output. It remains on
as long as the voltage remains above this set point.
OFF Delay
– Prevents the AUX output from turning on again
for a certain amount of time, even if the voltage rises above
the
Enable Voltage
set point again. This prevents nuisance
cycling of the
Divert DC
function.
Set Points
:
Enable Voltage
– Sets the high-voltage level at which the
function turns on the AUX output. It remains on for one
minute.
OFF Period
– Sets the delay time before the function turns
the AUX output on again.
Set Points
:
ON: Voltage
– Sets the low-voltage level at which the
Gen Alert
function turns on the AUX output.
Delay
– Sets the delay time after the
ON: Voltage
setting is
reached before the AUX output is turned on.
OFF: Voltage
– Sets the high-voltage level at which the
Gen Alert
function turns off the AUX output.
Delay
– Sets the delay time after the
OFF: Voltage
setting is
reached before the AUX output is turned off.