130 EVO Installation Guide
c. Connection for single zone input with end of line resistor (1000 ohms) OR
Connection for double serial zone input with end of line resistor (1000 ohms).
i Loop short 0.0V – 0.90V. (0 - 630 ohms total loop resistance)
ii Loop normal 1.10V – 1.40V. (770 - 1170 ohms)
iii Loop open 1.65V – 5.0V. (1430 to infinite ohms)
ADD THESE NOTES TO THE USER MANUAL
22. User
a. Cannot duplicate a user code or create a user code +/- 1.
23. System options
a. Siren squawk on arm/disarm with keypad.
i This features must be enabled to comply with CP-01 standards.
24. There is a communicator delay of 30 seconds in this control panel. It can be removed, or it can be increased
up to 45 seconds at the option of the end user by consulting with the Installer.
25. Keypad muting
a. Do not mute keypads to comply with CP-01 standards.
UNDOCUMENTED CHANGES
26. We stop the buzzer on all keypads upon entry of a code/action key. Its resume if the code is invalid or after
20 sec of no key pressed.
27. Create a quick reference chart or card to details all programming locations for the features in the standard
and their associated test procedures (walk test, test report).
28. A cancel event will be reported if an alarm is cancelled. The cancel window for that event is infinite (no time
limit).