114 EVO Installation Guide
Option [3] OFF=Beep disabled: Module and Combus Troubles
Option [3] ON=Beep enabled: Module and Combus Troubles
Option [4] OFF=Beep disabled: all Zone Troubles
Option [4] ON=Beep enabled: all Zone Troubles
C.0.38 Keypad Tamper Enable
SECTION [006]: OPTION [5]
Option [5] OFF=Keypad's tamper is disabled (default)
Option [5] ON=Keypad's tamper is enabled
C.0.39 Time Format
SECTION [005]: OPTION [7]
Option [7] OFF=Time uses the International time format (default).
Option [7] ON=Time uses the US time format.
C.0.40 Combus Voltmeter
1. From Normal Mode press and hold the [0] key.
2. Enter the [
INSTALLER CODE] (by default 000000).
3. Press [
ACC].
The voltage may drop during the control panel battery test.
Access Control Options
C.0.41 Assigning Doors To Partitions
SECTION [002]: OPTIONS [1] TO [8]
The Access Control door can be assigned to one or more partition(s) in the alarm system. This means that the
actions performed with the Access Control Card will be directly linked to the partition(s) assigned to that door.
Option [1] ON =Door assigned to Partition 1(default)
Option [2] ON =Door assigned to Partition 2
Option [3] ON=Door assigned to Partition 3
Option [4] ON =Door assigned to Partition 4
Option [5] ON=Door assigned to Partition 5
Option [6] ON=Door assigned to Partition 6
Option [7] ON=Door assigned to Partition 7
Option [8] ON=Door assigned to Partition 8
OFF = Access Control Cards will not be able to arm and/or disarm partitions from the door's reader
C.0.42 Unlock on REX (Request For Exit)
SECTION [006]: OPTION [8]
Option [8] OFF=Unlock on REX disabled (default)
Option [8] ON=Unlock on REX enabled
C.0.43 Door Unlocked Period
SECTION [008]
Enter any value between 001 and 255 to determine the seconds the door can remain unlocked. Default = 5 secs.