20 EVO Installation Guide
Note: The minimum permissible wire size to be employed shall be not smaller than No. 22 AWG (0.32 mm2).
Table 2: Milliamps (mA) Limitations For Each Run of Wire
Gauge: 18AWG, Surface: 0.823mm
2
Gauge: 22AWG, Surface: 0.326mm
2
Gauge: 24AWG, Surface: 0.205mm
2
Length of each
run of wire
Available
milliamps (mA)
Length of each
run of wire
Available
milliamps (mA)
Length of each
run of wire
Available
milliamps (mA)
30m(100ft.) 700 30m(100ft.) 700 30m(100ft.) 700
61m(200ft.) 700 61m(200ft.) 682 61m(200ft.) 429
91m(300ft.) 700 91m(300ft.) 454 91m(300ft.) 286
122m(400ft.) 700 122m(400ft.) 341 122m(400ft.) 214
152m(500ft.) 690 152m(500ft.) 273 152m(500ft.) 171
183m(600ft.) 575 183m(600ft.) 227 183m(600ft.) 143
213m(700ft.) 493 213m(700ft.) 195
244m(800ft.) 431 244m(800ft.) 170
274m(900ft.) 383 274m(900ft.) 151
305m(1000ft.) 345 305m(1000ft.) 136
457m(1500ft.) 230
610m(2000ft.) 172
762m(2500ft.) 138
914m(3000ft.) 115