EasyManuals Logo

Paradox EVO192 User Manual

Paradox EVO192
147 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
38 EVO Installation Guide
4.6.7 Intellizone Options
Use these options to enable or disable different Intellizone related options.
Figure 14: Delayed 24Hr Fire Zone
Partition 1: [3126] Partition 3: [3326] Partition 5: [3526] Partition 7: [3726]
Partition 2: [3226] Partition 4: [3426] Partition 6: [3626] Partition 8: [3826]
Option
Description
[1]
Intellizone Delay (default = disabled)
The zone stays in alarm for the entire Intellizone Delay.
[2]
Intellizone Double Knockout and Zone Crossing (default =
disabled)
The zone in alarm restores and reoccurs or an alarm occurs on
another zone defined as Intellizone
[3]
Intellizone Zone Crossing (default = disabled)
An alarm occurs on another zone defined as Intellizone.
[5]
Police Code is Generated on Zone Crossing Only (default =
disabled)
Latch alarm and transmit
report code as described
in section 4.4.13
Delayed Fire Zone
Triggered
Bell/siren silenced. Delay report
transmission an additional 90s.
Activate bell/siren output & delay
report transmission for 30s.
Has the zone
closed within
30s?
Yes
Yes
Yes
Yes
No
No
No
No
Has a 2
nd
Delayed Fire
Zone opened
in 30s?
Any key on
keypad
pressed
within 30s?
Problem
corrected?
END
Alarm Disabled

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Paradox EVO192 and is the answer not in the manual?

Paradox EVO192 Specifications

General IconGeneral
BrandParadox
ModelEVO192
CategorySmoke Alarm
LanguageEnglish

Related product manuals