38 EVO Installation Guide
4.6.7 Intellizone Options
Use these options to enable or disable different Intellizone related options.
Figure 14: Delayed 24Hr Fire Zone
Partition 1: [3126] Partition 3: [3326] Partition 5: [3526] Partition 7: [3726]
Partition 2: [3226] Partition 4: [3426] Partition 6: [3626] Partition 8: [3826]
Option
Description
[1]
Intellizone Delay (default = disabled)
The zone stays in alarm for the entire Intellizone Delay.
[2]
Intellizone Double Knockout and Zone Crossing (default =
disabled)
The zone in alarm restores and reoccurs or an alarm occurs on
another zone defined as Intellizone
[3]
Intellizone Zone Crossing (default = disabled)
An alarm occurs on another zone defined as Intellizone.
[5]
Police Code is Generated on Zone Crossing Only (default =
disabled)
Latch alarm and transmit
report code as described
in section 4.4.13
Delayed Fire Zone
Triggered
Bell/siren silenced. Delay report
transmission an additional 90s.
Activate bell/siren output & delay
report transmission for 30s.
Has the zone
closed within
30s?
Yes
Yes
Yes
Yes
No
No
No
No
Has a 2
nd
Delayed Fire
Zone opened
in 30s?
Any key on
keypad
pressed
within 30s?
Problem
corrected?
END
Alarm Disabled