C-25 Compliance
AC30 series Variable Speed Inverter
Frame G:
To access the filter disconnects the top and bottom covers will need to be removed, refer to Chapter 4 for removal information. Remove the
highlighted screws shown below. It is essential that all three ‘YCAP’ disconnect screws are in place, or all three are removed, do NOT remove
some of the disconnect screws.
Top Bottom
The screw should only be removed once the supply has been disconnected and the residual energy has been
discharged.
The product should never be powered or operated without the covers, the EMC filter disconnect will become
live once the screw is removed.
Not present on dc