Compliance C-26
AC30 series Variable Speed Inverter
Frame H:
To access the filter disconnects the top and bottom covers will need to be removed, refer to Chapter 4 for removal information. Remove the
highlighted screws shown below. It is essential that all three ‘YCAP’ disconnect screws are in place, or all three are removed, do NOT remove
some of the disconnect screws.
Top Bottom
The screws should only be removed once the supply has been disconnected and the residual energy has been
discharged.
“DANGER” – Risk of electric shock. Cover and cover screws must remain in place while drive is energised”,
the EMC filter disconnect will become live once cover and cover screws are removed.
Products
Not present on dc supplied
inverters
2 x YCAP Disconnects (first
remove control module see
page 4-18)
1 x VDR Disconnect (bottom
edge)