EasyManua.ls Logo

Parker AC30 - Page 467

Parker AC30
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Reference D-207
AC30 series Variable Speed Drive
PNO
Name
Path
Type
Default
Range
Units
WQ
View
Notes
MBus
0508
Quickstop Ramp Time
Parameters::Motor Control::Ramp
TIME
0.100
0.000 to 600.000
s
ALWAYS
TECHNICIAN
01543
0509
Final Stop Rate
Parameters::Motor Control::Ramp
REAL
1200
1 to 4800
Hz/s
ALWAYS
TECHNICIAN
01545
0511
Motor Type or AFE
Setup::Motor Control::Control and Type
Setup::Regen Control
Parameters::Control Mode::Control Mode
USINT
(enum)
0
0:INDUCTION MOTOR
1:PMAC MOTOR
STOPPED
TECHNICIAN
6
01549
0512
Control Strategy
Setup::Motor Control::Control and Type
Parameters::Control Mode::Control Mode
USINT
(enum)
0
0:VOLTS - HERTZ CONTROL
1:VECTOR CONTROL
STOPPED
TECHNICIAN
6
01551
0513
Active 33 - 64
Monitor::Trips
Parameters::Trips::Trips Status
DWORD
NEVER
OPERATOR
01553
0514
Warnings 33 - 64
Same as PNO 513
DWORD
NEVER
OPERATOR
01555
0515
Speed Loop Pgain
Parameters::Motor Control::Spd Loop Settings
REAL
20.00
0.00 to 3000.00
ALWAYS
TECHNICIAN
01557
0516
Speed Loop I Time
Parameters::Motor Control::Spd Loop Settings
TIME
0.100
0.001 to 1.500
s
ALWAYS
TECHNICIAN
01559
0517
Speed Loop Int Defeat
Parameters::Motor Control::Spd Loop Settings
BOOL
FALSE
ALWAYS
TECHNICIAN
01561
0518
Speed Loop Int Preset
Parameters::Motor Control::Spd Loop Settings
REAL
0
-500 to 500
ALWAYS
TECHNICIAN
01563
0519
Spd Loop Dmd Filt TC
Parameters::Motor Control::Spd Loop Settings
REAL
0.0
0.0 to 15.0
ms
ALWAYS
TECHNICIAN
01565
0520
Spd Loop Fbk Filt TC
Parameters::Motor Control::Spd Loop Settings
REAL
1.0
0.0 to 15.0
ms
ALWAYS
TECHNICIAN
01567
0521
Spd Loop Aux Torq Dmd
Parameters::Motor Control::Spd Loop Settings
REAL
0.00
-300.00 to 300.00
%
ALWAYS
TECHNICIAN
01569
0523
Spd Loop Adapt Thres
Parameters::Motor Control::Spd Loop Settings
REAL
0.00
0.00 to 10.00
%
ALWAYS
TECHNICIAN
01573
0524
Spd Loop Adapt Pgain
Parameters::Motor Control::Spd Loop Settings
REAL
20.00
0.00 to 300.00
ALWAYS
TECHNICIAN
01575
0525
Spd Demand Pos Lim
Parameters::Motor Control::Spd Loop Settings
REAL
110.00
-110.00 to 110.00
%
ALWAYS
TECHNICIAN
01577
0526
Spd Demand Neg Lim
Parameters::Motor Control::Spd Loop Settings
REAL
-110.00
-110.00 to 110.00
%
ALWAYS
TECHNICIAN
01579
0527
Sel Torq Ctrl Only
Parameters::Motor Control::Spd Loop Settings
BOOL
FALSE
ALWAYS
TECHNICIAN
01581
0528
Direct Input Select
Parameters::Motor Control::Spd Direct Input
USINT
(enum)
0
0:NONE
1:ANIN1
2:ANIN2
ALWAYS
TECHNICIAN
01583
0529
Direct Input Ratio
Parameters::Motor Control::Spd Direct Input
REAL
1.0000
-10.0000 to 10.0000
ALWAYS
TECHNICIAN
01585
0530
Direct Input Pos Lim
Parameters::Motor Control::Spd Direct Input
REAL
110.00
-110.00 to 110.00
%
ALWAYS
TECHNICIAN
01587
0531
Direct Input Neg Lim
Parameters::Motor Control::Spd Direct Input
REAL
-110.00
-110.00 to 110.00
%
ALWAYS
TECHNICIAN
01589
0533
Total Spd Demand RPM
Parameters::Motor Control::Spd Loop Diagnostics
REAL
x.xx
-100000.00 to 100000.00
RPM
NEVER
TECHNICIAN
01593
0534
Total Spd Demand %
Parameters::Motor Control::Spd Loop Diagnostics
REAL
x.xx
-200.00 to 200.00
%
NEVER
TECHNICIAN
01595
0535
Speed Loop Error
Parameters::Motor Control::Spd Loop Diagnostics
REAL
x.xx
-400.00 to 400.00
%
NEVER
TECHNICIAN
01597
0536
Speed PI Output
Parameters::Motor Control::Spd Loop Diagnostics
REAL
x.xx
-500.00 to 500.00
%
NEVER
TECHNICIAN
01599
0543
Power Stack Fitted
Parameters::Device Manager::Drive info
USINT
(enum)
0:NONE
1:3.5 A 400 V
2:4.5 A 400 V
3:5.5 A 400 V
4:7.5 A 400 V
5:10.0 A 400 V
6:12.0 A 400 V
7:16.0 A 400 V
8:23.0 A 400 V
9:32.0 A 400 V
10:38.0 A 400 V
11:45.0 A 400 V R1
12:60.0 A 400 V R1
13:73.0 A 400 V R1
14:87.0 A 400 V
15:105 A 400 V
16:145 A 400 V
17:180 A 400 V
18:205 A 400 V
19:260 A 400 V
20:45.0 A 400 V
21:60.0 A 400 V
22:73.0 A 400 V
23:315 A 400 V
24:380 A 400 V
25:440 A 400 V
NEVER
TECHNICIAN
01613
0555
PMAC Max Speed
Setup::Motor Control::Motor Data PMAC
Parameters::Motor Control::PMAC Motor Data
REAL
3000
0 to 100000
RPM
ALWAYS
TECHNICIAN
6
01637
0556
PMAC Max Current
Same as PNO 555
REAL
4.50
0.00 to 5000.00
A
ALWAYS
TECHNICIAN
6
01639
0557
PMAC Rated Current
Same as PNO 555
REAL
4.50
0.00 to 5000.00
A
ALWAYS
TECHNICIAN
6
01641
0558
PMAC Rated Torque
Same as PNO 555
REAL
4.50
0.00 to 30000.00
Nm
ALWAYS
TECHNICIAN
6
01643
0559
PMAC Motor Poles
Same as PNO 555
UINT
10
0 to 400
ALWAYS
TECHNICIAN
6
01645
0560
PMAC Back Emf Const KE
Same as PNO 555
REAL
60.0
0.0 to 30000.0
V
ALWAYS
TECHNICIAN
6
01647
0561
PMAC Winding Resistance
Same as PNO 555
REAL
6.580
0.000 to 50.000
Ohm
ALWAYS
TECHNICIAN
6
01649
0562
PMAC Winding Inductance
Same as PNO 555
REAL
20.00
0.00 to 1000.00
mH
ALWAYS
TECHNICIAN
6
01651

Table of Contents

Other manuals for Parker AC30