F-9 Technical Specifications
AC30 series Variable Speed Drive
Power Supply = 380-480V ±10%, 50/60Hz 5%
Motor power, output current and input current must not be exceeded under steady state operating conditions.
Minimum repetitive power up / power down cycle time = 10 mins
Product Code
Motor Power
Output
Current
(A)
Input
Current
(A)
Estimated
Efficiency
Switching Frequency
(kHz)
nominal / maximum
Output Current Derate %/kHz
(applied above nominal
switching frequency)
FRAME K : Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac input. Prospective short circuit current 18kA.
Normal Duty (Output Overload Motoring 110% for 60s)
31x-4K0315…
160kW
315
276
98%
2 / 8
8.5%
250Hp
302
279
31x-4K0380…
200kW
380
343
98%
2 / 8
7.7%
300Hp
361
333
31x-4K0440…
250kW
440
428
98%
2 / 8
8.3%
350Hp
414
389
Heavy Duty (Output Overload Motoring 150% for 60s, 180% for 3s short term rating)
31x-4K0315…
132kW
260
229
98%
2 / 8
7.7%
200Hp
240
225
31x-4K0380…
160kW
315
276
98%
2 / 8
6.9%
250Hp
302
279
31x-4K0440…
200kW
380
344
98%
2 / 8
7.5%
300Hp
361
334