Saia-Burgess Controls AG
Manual Manual PCD 1 / PCD 2 Series │ Document 26 / 737 EN22 │ 2013-11-26
5
Input/output (I/O) modules
5-55
Analogue input modules
Technical data for add-on modules (variant modules)
PCD2.W110 4 inputs for Pt 100 probes
Current sources 2 mA
Measuring range  -50 °C … +150 °C
Accuracy of measurement better than 0.2 °C
PCD2.W111 4 inputs for Ni 100 probes
Current sources 2 mA
Measuring range   -50 °C … +150 °C
Accuracy of measurement better than 0.4 °C
PCD2.W112 4 inputs for Pt 1000 probes
Current sources 0.2 mA
Measuring range  -50 °C … +150 °C
Accuracy of measurement better than 0.2 °C
PCD2.W113 4 inputs for Ni 1000 probes
Current sources 0.2 mA
Measuring range  -  -50 °C … +150 °C
Accuracy of measurement better than 0.4 °C
PCD2.W114 4 inputs for Pt 100 probes
Current sources 0.2 mA
Measuring range  0 °C … +350 °C
Accuracy of measurement better than 0.4 °C
Accuracy of measurements
The curves below show the maximum measurement error
(measurement and repeating accuracy).
Total error = linearization error + repeating error
Each channel is calibrated to the minimum and maximum values:
-50 °C 0 + 2 LSB
+150 °C 4095 - 2 LSB
For these two values, the measurement error = 0.