Saia-Burgess Controls AG
Manual Manual PCD 1 / PCD 2 Series │ Document 26 / 737 EN22 │ 2013-11-26
5
Input/output (I/O) modules
5-58
Analogue input modules
Wiring
All unused inputs must be short-circuited: +I to -I in each case
Output circuits and terminal designation
Programming
Classic: Programming examples for the PCD2.W11x can be found in a separate
manual and on the TCS Support site (www.sbc-support.com + getting started).
xx7: the rmware reads in the values according to the conguration (I/O Builder)
Watchdog: This module can be used on all base addresses; there is no interaction with the
watchdog on the CPUs. For details, please refer to the “Watchdog” section, which describes
the correct use of the watchdog in conjunction with PCD2 components.