EasyManua.ls Logo

SICK microScan3

SICK microScan3
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Use Data type Definition Values Safety implica‐
t
ion
TriggerResetCutOffPath01 Safety function BOOL Reset Cut-off path 01
Reset of cut-off path 01
after activation of the
restart interlock
0 = no reset Safety-relevant
parameter
0-1-0 = reset
(dur
ation of sta‐
tus 1 ≥ 60 ms)
TriggerResetCutOffPath02
T
riggerResetCutOffPath08
Safety function BOOL Reset Cut-off path 02
… 08
Reset of cut-off path 02
… 08 after activation of
the restart interlock
1)
0 = no reset Safety-relevant
parameter
0-1-0 = reset
(duration of sta‐
tus 1 ≥ 60 ms)
TriggerRunMode Safety function BOOL Start safety function
R
estarts the safety
function, e.g. if it
was stopped or after
an application error.
(The device must be
restarted after a device
error.)
0 = no start com‐
mand
Safety-relevant
parameter
0-1-0 = start
safety function
(duration of sta‐
tus 1 ≥ 120 ms)
1 = ignored
1)
Cut-off paths 5 to 8 are only available for the Pro performance package.
13.6.1.1.2 Output of the device (input of the control)
Table 50: Output of the device (input of the control)
Name Use Data type Definition Values Safety implica‐
t
ion
ApplicationError Diagnostics BOOL Application error
S
ignals whether an
application error is
present, causing the
safety function to be
paused. To resolve this,
rectify the cause of the
error and then restart
the safety function.
0 = no applica‐
tion error
Parameter with‐
out safety impli‐
cation
1 = application
error
ContaminationError Diagnostics BOOL Contamination error
Opt
ics cover is dirty. All
safety outputs in the
OFF state. Clean the
optics cover.
0 = no contami‐
nation error
Parameter with
implication for
the safety func‐
tion
1 = contamina‐
tion error
ContaminationWarning Diagnostics BOOL Contamination warning
Opt
ics cover is dirty.
Clean the optics cover.
0 = no contami‐
nation warning
Parameter with‐
out safety impli‐
cation
1 = contamina‐
tion warning
CurrentMonitoringCaseNoTa‐
ble1
Diagnostics USINT Current monitoring
case (Monitoring case
table 1)
Signals the current
(active) monitoring case
of monitoring case
table 1.
0 = no monitor‐
ing case is active
Parameter with‐
out safety impli‐
cation
1 … 254 = num‐
ber of t
he current
(active) monitor‐
ing case
TECHNICAL DATA 13
8021219/1ELL/2022-01-21 | SICK O P E R A T I N G I N S T R U C T I O N S | microScan3 – PROFINET
179
Subject to change without notice

Table of Contents

Other manuals for SICK microScan3

Related product manuals