Name Use Data type Definition Values Safety implica‐
t
ion
TriggerResetCutOffPath01 Safety function BOOL Reset Cut-off path 01
Reset of cut-off path 01
after activation of the
restart interlock
0 = no reset Safety-relevant
parameter
0-1-0 = reset
(dur
ation of sta‐
tus 1 ≥ 60 ms)
TriggerResetCutOffPath02
T
riggerResetCutOffPath08
Safety function BOOL Reset Cut-off path 02
… 08
Reset of cut-off path 02
… 08 after activation of
the restart interlock
1)
0 = no reset Safety-relevant
parameter
0-1-0 = reset
(duration of sta‐
tus 1 ≥ 60 ms)
TriggerRunMode Safety function BOOL Start safety function
R
estarts the safety
function, e.g. if it
was stopped or after
an application error.
(The device must be
restarted after a device
error.)
0 = no start com‐
mand
Safety-relevant
parameter
0-1-0 = start
safety function
(duration of sta‐
tus 1 ≥ 120 ms)
1 = ignored
1)
Cut-off paths 5 to 8 are only available for the Pro performance package.
13.6.1.1.2 Output of the device (input of the control)
Table 50: Output of the device (input of the control)
Name Use Data type Definition Values Safety implica‐
t
ion
ApplicationError Diagnostics BOOL Application error
S
ignals whether an
application error is
present, causing the
safety function to be
paused. To resolve this,
rectify the cause of the
error and then restart
the safety function.
0 = no applica‐
tion error
Parameter with‐
out safety impli‐
cation
1 = application
error
ContaminationError Diagnostics BOOL Contamination error
Opt
ics cover is dirty. All
safety outputs in the
OFF state. Clean the
optics cover.
0 = no contami‐
nation error
Parameter with
implication for
the safety func‐
tion
1 = contamina‐
tion error
ContaminationWarning Diagnostics BOOL Contamination warning
Opt
ics cover is dirty.
Clean the optics cover.
0 = no contami‐
nation warning
Parameter with‐
out safety impli‐
cation
1 = contamina‐
tion warning
CurrentMonitoringCaseNoTa‐
ble1
Diagnostics USINT Current monitoring
case (Monitoring case
table 1)
Signals the current
(active) monitoring case
of monitoring case
table 1.
0 = no monitor‐
ing case is active
Parameter with‐
out safety impli‐
cation
1 … 254 = num‐
ber of t
he current
(active) monitor‐
ing case
TECHNICAL DATA 13
8021219/1ELL/2022-01-21 | SICK O P E R A T I N G I N S T R U C T I O N S | microScan3 – PROFINET
179
Subject to change without notice

Table of Contents

Other manuals for SICK microScan3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK microScan3 and is the answer not in the manual?

SICK microScan3 Specifications

General IconGeneral
Scanning angle275°
Power supply24 V DC
Supply voltage24 V DC ± 20%
Enclosure ratingIP65
Resolution70 mm
Protective field range5.5 m
Number of fields128
InterfaceEthernet
Safety integrity levelSIL3
Performance levelPL e
Ambient temperature+50°C
Scanning range5.5 m