5.6 Restoring the factory setting
There are cases where something goes wrong when commissioning a drive system e.g.:
The line voltage was interrupted during commissioning and you were not able to complete
commissioning.
You got confused during the commissioning and you can no longer understand the
individual settings that you made.
You do not know whether the inverter was already operational.
In cases such as these, reset the inverter to the factory settings.
Restore the factory inverter settings
Procedure with STARTER
Proceed as follows to reset the inverter to factory settings:
1. Select your drive.
2. Go online.
3. Open "Drive Navigator".
4. Select the "Commissioning" button.
5. Press the "Factory setting" button.
6. ☑ In the screen form, select "After loading copy RAM to ROM".
7. Start the reset.
8. Wait until the inverter has been reset to the factory setting.
You have reset the inverter to factory settings.
Procedure with Startdrive
Proceed as follows to reset the inverter to factory settings:
1. Go online.
2. Select "Commissioning".
3. Select "Backing up/reset".
4. Select "All parameters are reset".
Commissioning
5.6 Restoring the factory setting
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 189

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals