10.7 Technical data, PM250 Power Module
Typical inverter load cycles
VORDGF\FOHEDVHGRQ
+LJK2YHUORDG
VORDGF\FOHEDVHGRQ
/RZ2YHUORDG
,
/2
,
/2
,
+2
,
/2
,
VVV
V
W>V@
,
+2
,
,
+2
VVV
V
W>V@
10.7.1 Ambient conditions
Ambient conditions during operation
Property Version
Ambient conditions for transport in the transport packaging
Climatic ambient conditions ‑ 40° C … + 70° C, according to Class 2K4 to EN 60721‑3‑2
maximum humidity 95% at 40° C
Mechanical ambient condi‐
tions
FSC: Shock and vibration permissible according to 1M2 to EN 60721‑3‑2
FSD … FSF: Shock and vibration permissible according to 2M3 to EN 60721‑3‑2
Protection against chemical
substances
Protected according to Class 2C2 to EN 60721‑3‑2
Biological ambient condi‐
tions
Suitable according to Class 2B1 to EN 60721‑3‑2
Ambient conditions for long-term storage in the product packaging
Climatic ambient conditions ‑ 25° C … + 55° C, according to Class 1K3 to EN 60721‑3‑1
Protection against chemical
substances
Protected according to Class 1C2 to EN 60721‑3‑1
Biological ambient condi‐
tions
Suitable according to class 1B1 to EN 60721‑3‑1
Ambient conditions in operation
Installation altitude Up to 1000 m above sea level without limitations
Restrictions for special ambient conditions (Page 510)
Technical data
10.7 Technical data, PM250 Power Module
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 503