Application example: Changing the function of a digital output
To output inverter fault messages via digital output DO 1, you
must interconnect DO1 with these fault messages.
Set p0731 = 52.3
Advanced settings
You can invert the signal of the digital output using parameter p0748.
For more information, please see the parameter list and the function block diagrams 2230 f of
the List Manual.
Overview of the manuals (Page 537)
Advanced commissioning
6.3 Adapt the default setting of the terminal strip
Converter with the CU230P-2 Control Units
202 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE