Parameter Remark
p11065 Free tec_ctrl 0 actual value smoothing time constant (Factory setting: 0 s)
p11067 Free tec_ctrl 0 actual value upper limit (Factory setting: 100 %)
p11068 Free tec_ctrl 0 actual value lower limit (Factory setting: -100%)
p11071 Free tec_ctrl 0 actual value inversion (Factory setting: 0)
0: No inversion
1: Inversion
p11074 Free tec_ctrl 0 differentiation time constant (T
d
) (Factory setting: 0 s)
p11080 Free tec_ctrl 0 proportional gain (K
P
) (Factory setting: 1.0)
p11085 Free tec_ctrl 0 integral time (T
I
) (Factory setting: 30 s)
p11091 CO: Free tec_ctrl 0 maximum limit (Factory setting: 100 %)
p11092 CO: Free tec_ctrl 0 minimum limit (Factory setting: 0 %)
r11094 CO: Free tec_ctrl 0 output signal
You can find the complete parameter list in the List Manual.
Advanced commissioning
6.19 Free technology controllers
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 283