If it is not possible to temporarily reduce the pulse frequency, or the measure cannot prevent
a power unit thermal overload, then the inverter switches off the motor with fault F30024.
Overload response for p0290 = 12
The inverter responds in two stages:
1. If you operate the inverter with increased pulse frequency setpoint p1800, then the inverter
reduces its pulse frequency starting at p1800.
There is no current derating as a result of the higher pulse frequency setpoint.
Once the overload condition has been removed, the inverter increases the pulse frequency
back to the pulse frequency setpoint p1800.
2. If it is not possible to temporarily reduce the pulse frequency, or the risk of inverter thermal
overload cannot be prevented, then stage 2 follows:
In vector control, the inverter reduces the output current.
In U/f control, the inverter reduces the speed.
Once the overload condition has been removed, the inverter re-enables the output current
or speed.
If both measures cannot prevent a power unit thermal overload, then the inverter switches off
the motor with fault F30024.
Overload response for p0290 = 13
We recommend this setting for drives with high starting torque, e.g. horizontal conveyors or
extruders.
If you operate the inverter with increased pulse frequency, then the inverter reduces its pulse
frequency starting at the pulse frequency setpoint p1800.
There is no current derating as a result of the higher pulse frequency setpoint.
Once the overload condition has been removed, the inverter increases the pulse frequency
back to the pulse frequency setpoint p1800.
If it is not possible to temporarily reduce the pulse frequency, or the measure cannot prevent
a power unit thermal overload, then the inverter switches off the motor with fault F30024.
Special feature for PM330
For PM330, the overload response is permanently set to p0290 = 2. It cannot be changed.
Advanced commissioning
6.27 Inverter protection using temperature monitoring
Converter with the CU230P-2 Control Units
324 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals