The motor is now operated directly on the line supply. A multiple of the motor rated current
can flow before the motor speed has reached the line frequency.
Switching from line operation to inverter operation
1. The inverter opens the K2 line contactor via a digital output.
2. The inverter waits for the unlocking time of the motor.
3. The inverter waits for the feedback that the K2 line contactor is open.
4. The inverter closes the K1 inverter contactor via a digital output.
5. The inverter switches the motor ON.
6. The inverter adjusts with the "Flying restart" function its output frequency to the speed of
the motor.
The motor is now operated on the inverter.
How is the changeover triggered?
The following options are provided to switch between inverter operation and line operation:
Changeover for activation via a control command
Changeover depending on the speed
Advanced commissioning
6.36 Bypass
Converter with the CU230P-2 Control Units
352 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals