Parameter Description
r0039 Energy display [kWh]
[0] Energy balance
Energy usage since the last reset
[1] Energy drawn since the last reset
[2] Energy fed back since the last reset
p0040 Reset energy consumption display
A signal change 0 → 1 sets r0039[0…2] = 0, r0041 = 0 and r0042 = 0.
r0041 Energy consumption saved (kWh)
Energy saved referred to 100 operating hours.
For less than 100 operating hours, the inverter interpolates the energy saving to 100
operating hours.
r0042 CO: Process energy display [1 ≙ 1 Wh]
For display as process variable. Enable with p0043.
[0] Energy balance
Energy consumption since the last reset.
[1] Energy drawn since the last reset
[2] Energy fed back since the last reset.
p0043 BI: Enable energy usage display
1 signal: Process energy display is active in r0042.
p3320 …
p3329
Flow characteristic
6SHHGLQ
3RZHULQ
6SHHGSRZHU
SS
SS
SS
SS
SS
Factory setting of the flow characteristic
To set the characteristic, you require the following data from the machine manufacturer
for each speed interpolation point:
● The flow rate of the fluid-flow machine associated with the 5 selected inverter speeds
● The power drawn at constant speed associated with the five flow rates corresponds
to the line frequency and mechanical throttling of the flow rate.
Advanced commissioning
6.39 Calculating the energy saving for fluid flow machines
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 365