EasyManuals Logo

Siemens CU240B-2 Operating Instructions

Siemens CU240B-2
550 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #389 background imageLoading...
Page #389 background image
STARTER does not display any screen forms.
Adjustable parameters cannot be changed using commissioning tools, e.g. an operator
panel or Startdrive.
When know-how protection is active, support can only be provided (from Technical Support)
after prior agreement from the machine manufacturer (OEM).
Adjustable parameters that can be changed when know-how protection is active
Several adjustable parameters can be read and changed when know-how protection is active.
You can find a list of the adjustable parameters that can be read and changed in the List Manual
under "KHP_WRITE_NO_LOCK".
In addition, you can define an exception list of adjustable parameters, which end users may
change.
Adjustable parameters that can be read when know-how protection is active
Several adjustable parameters can be read but not changed when know-how protection is
active. You can find a list of the adjustable parameters that can be read in the List Manual
under "KHP_ACTIVE_READ".
Functions that are inhibited when know-how protection is active
Active know-how protection inhibits the following functions:
Download of inverter settings using STARTER or Startdrive
Automatic controller optimization
Stationary or rotating measurement of the motor data identification
Deleting the alarm history and the fault history
Generating acceptance documentation for the safety functions
Functions that can be executed when know-how protection is active
The following functions can be executed when know-how protection is active:
Restoring the factory setting
Acknowledging faults
Displaying faults, alarms, fault history and alarm history
Reading out the diagnostic buffer
Controlling the inverter via the control panel in STARTER or Startdrive
Uploading adjustable parameters that can be changed or read when know-how protection
is active
Displaying the generated acceptance documentation for the safety functions
Depending on the know-how protection settings, the trace function in STARTER can also be
active when know-how protection is active.
Saving the settings and series commissioning
7.6 Know-how protection
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 389

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals