Parameter Description
r2123 Alarm time received in milliseconds
Displays the time in milliseconds when the alarm occurred
r2124 Alarm value
Displays additional information about the alarm
r2125 Alarm time removed in milliseconds
Displays the time in milliseconds when the alarm was removed
r2145 Alarm time received in days
Displays the time in days when the alarm occurred
r2132 Actual alarm code
Displays the code of the alarm that last occurred
r2134 Alarm value for float values
Displays additional information about the alarm that occurred for float values
r2146 Alarm time removed in days
Displays the time in days when the alarm was removed
Extended settings for alarms
Parameter Description
You can change up to 20 different alarms into a fault or suppress alarms:
p2118[0 … 19
]
Setting the message number for the message type
Selection of the alarms for which the message type should be changed
p2119[0 … 19
]
Setting the message type
Setting the message type for the selected alarm
1: Fault
2: Alarm
3: No message
You will find details in function diagram 8075 and in the parameter description of the List
Manual.
Alarms, faults and system messages
8.4 Alarms, alarm buffer, and alarm history
Converter with the CU230P-2 Control Units
402 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE