Table 10-35 PM330, frame size JX, 3 AC 500 V … 690 V
Article No. 6SL3310- 1PG35-8AA0 1PG36-5AA0 1PG37-2AA0
Rated input current
- at 500 V, 45 °C
- at 600 V, 45 °C
- at 690 V, 45 °C
- at 500 V, 55 °C
- at 600 V, 55 °C
- at 690 V, 55 °C
596 A
578 A
555 A
506 A
492 A
472 A
679 A
647 A
618 A
577 A
550 A
525 A
753 A
720 A
690 A
640 A
612 A
587 A
Rated input current DCP/DCN
(for 2/3 of the inverter power)
- at 675 V
DC
, 45 °C
- at 810 V
DC
, 45 °C
- at 930 V
DC
, 45 °C
- at 675 V
DC
, 55 °C
- at 810 V
DC
, 55 °C
- at 930 V
DC
, 55 °C
495 A
474 A
456 A
420 A
403 A
387 A
557 A
531 A
507 A
473 A
451 A
431 A
617 A
590 A
566 A
525 A
502 A
481 A
Rated output current I
N
- at 500 V, 45 °C
- at 600 V, 45 °C
- at 690 V, 45 °C
- at 500 V, 55 °C
- at 600 V, 55 °C
- at 690 V, 55 °C
581 A
557 A
535 A
494 A
473 A
455 A
654 A
623 A
595 A
555 A
530 A
506 A
725 A
693 A
665 A
616 A
589 A
565 A
LO base load power
LO base load input current at 690 V
LO base load output current at 690 V
500 kW
540 A
520 A
560 kW
602 A
580 A
630 kW
675 A
650 A
HO base load power
HO base load input current at 690 V
HO base load output current at 690 V
450 kW
461 A
444 A
500 kW
494 A
476 A
560 kW
552 A
532 A
Fuse according to IEC
manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1437-2
(710 A/690 V)
Siemens AG
≤ 100 kA
> 10.0 kA
3NE1438-2
(800 A/690 V)
Siemens AG
≤ 100 kA
> 11.0 kA
3NE1448-2
(850 A/690 V)
Siemens AG
≤ 100 kA
> 13.0 kA
Fuse in compliance with UL
2)
Manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1437-2
(710 A/690 V)
Siemens AG
≤ 100 kA
> 10.0 kA
3NE1438-2
(800 A/690 V)
Siemens AG
≤ 100 kA
> 11.0 kA
3NE1448-2
(850 A/690 V)
Siemens AG
≤ 100 kA
> 13.0 kA
max. power loss, at I
N
, 45 °C, 690 V 8.134 kW 8.828 kW 9.937 kW
Required cooling air flow 450 l/s 450 l/s 450 l/s
Maximum connectable cross-section of the power
cable
6 x 240 mm
2
6 x 500 kcmil
6 x 240 mm
2
6 x 500 kcmil
6 x 240 mm
2
6 x 500 kcmil
Maximum connectable cross-section of the motor
cable
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
Maximum connectable cross-section of the DC link
cable
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
Technical data
10.5 Technical data, PM330 Power Module
Converter with the CU230P-2 Control Units
474 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals