Technical data
10.3 Technical data, Power Modules
Converter with the CU240B-2 and CU240E-2 Control Units
450 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Table 10- 27 PM240-2, IP20, FSF, 3 AC 500 V … 690 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
132 kW
137 A
HO base load power
HO base load input current
HO base load output current
110 kW
122 A
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NE1 225-0 / 200 A
Power loss without filter
2.56 kW
Required cooling air flow
Weight without filter
60 kg
LO base load output current for a pulse frequency of …
[A]
6SL3210-1PH31-0❒L0
60
6SL3210-1PH31-4❒L0
85.2
The permissible motor cable length depends on the particular cable type and the pulse frequency that
has been selected