Commissioning and Diagnostics
5-38
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
5.6.7 Module status
Definition
The module status indicates the status of the configured modules and provides
details of the ID-specific diagnosis in respect of the configuration. The module
status begins after the module diagnosis and comprises 7 bytes.
The module is only contained in the diagnosis frame if you have activated
”extended diagnosis” during parameterization.
Module status
The module status for ET 200X is configured as follows:
Byte 9
Byte 10
Byte 11
70
0
H
0
H
Byte 12
Status
type:
Module
status
Always
”0”
Always
”0”
Byte 13
7
I/O section of the basic module
6
Byte 14
70
1
Expansion module 1
Expansion module 2
Expansion module 3
Expansion module 4
23456
00
B
: Module OK;
valid data
01
B
: Module fault;
invalid data
(module defective)
10
B
: Incorrect module;
invalid data
11
B
: no module;
invalid data
70
123456
1
00
11
000
Length of the module status
incl. byte 9 (= 7 bytes)
Code for station diagnosis
70
123456
00
11
000
0
2
H
= Module status
Code for status message
Byte 15
70
1
Expansion module 5
Expansion module 6
Expansion module 7
23456
00
00000
0
Figure 5-10 Configuration of the module status for ET 200X