Technical Specifications
7-20
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
Parameters
The following table provides an overview of the parameters that can be set on the
basic module.
Table 7-9 Parameters of the BM 142 DO 4DC 24V/2A
Parameters
Range Default Area
S7 slave with
HWCONFIG
Standard slave
with DDB file
SIEM803C.GSG
1
Standard slave
with DDB file
SI03803C.GSG
1
affected
––– ––– DP interrupt mode DPV0/DPV1 DPV1 ET 200X
Diagnostic interrupt Yes/no Yes ET 200X
Hardware interrupt Yes/no Yes ET 200X
––– Enhanced
diagnostics
2
–––
Yes/no Yes ET 200X
––– ––– Startup when
expected/actual
config. differ
Yes/no No ET 200X
Diagnosis: no load voltage (S) Yes/no Yes ET 200X
––– ––– Module diagnosis Yes/no Yes ET 200X
––– ––– Module status Yes/no Yes ET 200X
––– ––– Channel-specific
diagnosis
Yes/no Yes ET 200X
1
As of basic module 6ES7 142-1BD22-0XB0, version 3
2
The length of the diagnostic frame is 32 bytes.
Dimensions and weight
Dimensions
W H D (mm)
134 110 55
Weight Approx. 500 g
Module-specific data
Baud rate 9.6/19.2/93.75/187.5
/500 kbps
1.5/3/6/12 Mbps
Bus protocol PROFIBUS-DP
FREEZE compatibility Yes
SYNC compatibility Yes
Number of outputs 4
Cable length
Unshielded Max. 30 m
Manufacturer identification 803C
H