Commissioning and Diagnostics
5-42
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
Table 5-21 Channel-specific error messages manufacturer-specific
Error type
Error text Meaning Action
10000
B
16
D
Parameteriz
ation error
Parameter assignment error, for example, because:
The module cannot use the parameter
(unknown, impermissible combination...)
Module is not parameterized.
Correct the
parameter
assignment.
10001
B
17
D
Load
voltage is
missing
The following voltages may be missing:
Load voltage at BM 141/BM 142
Switched load voltage in the case of BM 143
DESINA and BM 141-ECOFAST 8DI
Correct the
process wiring
10110
B
22
D
Hardware
interrupt lost
Hardware interrupt lost Correction,
coordination of
program, process,
module
11000
B
24
D
Actuator
fault
Excess temperature on motor Check mechanical
loading of motor
Thermistor not connected Connect thermistor
or deactivate
thermistor
monitoring, motor
parameter on
EM 148-FC
11010
B
26
D
External
fault
External (process-related) error, for example:
Sensor error
Actuator error
Sensor data is not correct
Break in wire to EM
Replace the
sensor/actuator;
correct the process
wiring.