Installation
3-16
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
3.3 Setting/modifying the PROFIBUS address
The PROFIBUS address defines the address of the ET 200X distributed I/O device
on PROFIBUS-DP which is used by the DP master.
Set the PROFIBUS address using the DIP switches on the basic module.
Valid PROFIBUS addresses
The PROFIBUS address can be anything from 1 to 125. The PROFIBUS address
0, which is set when the ET 200 distributed I/O system leaves the factory, is
reserved for a programming device/PC.
Location of the DIP switches on the BM 141, BM 142 and BM 147/CPU
The DIP switches for setting the PROFIBUS address are inside the basic module
underneath the connector plate for the connectors for PROFIBUS-DP and the
supply voltage.
Location of the DIP Switches on the BM 143-DESINA and BM 141-ECOFAST
The DIL switches for setting the PROFIBUS address are in a removable
configuration connector.
The configuration connector is secured to the basic module by an 8-pin M12 round
plug.
This means that if the basic module has to be replaced it is not necessary to reset
the PROFIBUS address.