Commissioning
5.3 Procedure for commissioning via STARTER
Inverter chassis units
156 Operating Instructions, 07/2016, A5E00331449A
Selecting drive functions
Figure 5-28 Selecting drive functions
Select the required data:
Technological application:
"(0) Standard drive (VECTOR)"
Edge modulation is not enabled.
The dynamic voltage reserve is increased (10 V), which reduces the maximum output
voltage.
"(1) Pumps and fans"
(default setting)
Edge modulation is enabled.
The dynamic voltage reserve is reduced (2 V), which increases the maximum output
voltage.
"(2) Sensorless control down to f = 0 (passive loads)"
Closed-loop controlled operation down to zero speed is possible for passive loads.
These include applications in which the load cannot produce a regenerative torque on
startup and the motor comes to a standstill when pulses are inhibited.