Commissioning
5.3 Procedure for commissioning via STARTER
Inverter chassis units
166 Operating Instructions, 07/2016, A5E00331449A
7. Set the IP address of the PG/PC access interface to the Control Unit to 169.254.11.1 and
the subnet mask to 255.255.0.0.
Figure 5-35 Internet Protocol (TCP/IP) properties
8. Click "OK" and close the Windows-specific window of the network connections.
Assigning the IP address and the name via STARTER, "Accessible nodes" function
Use the STARTER to assign an IP address and a name to the Ethernet interface.
1. Connect the PG/PC and the Control Unit using an Ethernet cable.
2. Switch on the Control Unit.
3. Open STARTER.
4. Create a new project or open an existing project.
5. Search for available nodes in Ethernet via Project -> Accessible nodes or the "Accessible
nodes" button.