Commissioning
5.5 First commissioning with the AOP30
Inverter chassis units
178 Operating Instructions, 07/2016, A5E00331449A
Basic commissioning: Entering the basic parameters
Entering the basic commissioning parame-
ters
:
If a sine
-wave filter is connected, it must be
activated in p0230 (p0230 = 3/4). Otherwise, it
could be damaged.
p0700: Preset command source
1: PROFIdrive
2: TM31 terminals
3: CU terminals
4: PROFIdrive+TM31
p1000: Preset setpoint source
1: PROFIdrive
2: TM31 terminals
3: Motorized potentiometer
4: Fixed setpoint
Once a setpoint source has
been selected
(p1000), the main setpoint p1070 is defaulted
accordingly.
To navigate through the selection fields,
choose <F2> or <F3>.
To activate a selection, choose <F5>.
To change a parameter value, navigate to the
required selection field and activate
with
<F5>.
Another window appears in which you can
-
enter the required value directly, or
-
select the value from a list.
Final confirmation
Confirm the basic parameters to save them.
Once you have selected "Continue" and act
i-
vated your entries with <F5>, the ba
sic pa-
rameters you entered are permanently saved
and the calculations required for closed
-loop
control are carried out.