Operation
6.8 Communication via PROFINET IO
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
269
Table 6- 24 Parameter designation, assignment and meaning
I&M parameter des-
ignation
I&M 0:
IM_SUPPORTED
- - - r8820[62,63] The parameter indicates which I&M data sets
are supported.
The value 0x1E indicates that I&M data sets
I&M 1:
Visible
32 Space
p8806[0...31] Text that identifies the function or task of the
I&M 1:
Visible
22 Space
p8806[32...53
Text that identifies the device location.
I&M 2:
INSTALLATION_DAT
E
Visible
string
16 Space
0x20…0x7E
p8807[0...15] Text with the date of the installation or the
initial commissioning of the device. The follow-
ing date formats are supported:
• YYYY-MM-DD
• YYYY-MM-DD hh:mm
– YYYY: Year
– MM: Month 01...12
– DD: Day 01...31
– hh: Hours 00...23
– mm: Minutes 00...59
The separators between the individual specifi-
cations, i.e. hyphen '-', blank ' ' and colon ':',