Operation
6.8 Communication via PROFINET IO
Inverter chassis units
270 Operating Instructions, 07/2016, A5E00331449A
I&M parameter des-
ignation
I&M 3:
Visible
54 Space
p8808[0...53] Text with any comments or notes.
I&M 4: SIGNATURE Octet
string
54 Space
0x00…0x00
p8809[0...53] The parameter can be filled automatically by
the system, in which case it contains a stand-
ard value, namely, a functional check signature
for the change tracking by Safety Integrated.
The check signature has the following format:
• The first four octets (0...3) contain the con-
tent of parameter r9781 index 0: "SI change
monitoring checksum (Control Unit)".
• The second four octets (4...7) contain the
content of parameter r9782 index 0: "SI
change monitoring time stamp (Control
Unit)".
• The remainder (octets 8...53) contains
zeroes.
Alternatively, a user can enter a user value
from an application and so overwrite the
standard value. Parameter p8805 specifies
which value is entered in p8809:
• p8805 = 0 standard value entered
• p8805 = 1 user value entered
When p8805 = 0 is set, the standard setting for
The I&M data sets 1...4 are stored permanently in parameters p8806...p8809. Significant
properties of these four parameters:
● They can be displayed in the STARTER expert list.
● The SINAMICS "Reset parameter" (p0976 = 1, p0970 = 1) function does not have any
effect on the content of parameters.
● I&M data sets are not changed when the alternative parameter sets are stored or loaded.
The transfer of parameter sets between a memory card and non-volatile device memory
does not have any effect on the I&M data sets.
p8805[0...1]
Identification and Maintenance configuration
p8806[0...53]
aintenance 1
p8807[0...15]
Identification and Maintenance
2
p8808[0...53]
Identification and Maintenance
3
r8809[0...53]
Identification and Maintenance
4