Operation
6.10 Communication via EtherNet/IP
Inverter chassis units
288 Operating Instructions, 07/2016, A5E00331449A
Table 6- 32 Explanation for No. 5 of the previous table
1 0 Owned 0: Inverter is not assigned to any master
1: Inverter is assigned to a master
1 Reserved
2 Configured 0: EtherNet/IP basic settings
1: Modified EtherNet/IP settings
4 … 7 Extended De-
vice Status
0: Self-test or status not known
1: Firmware update active
2: At least one I/O connection with error
3: No I/O connections
4: Incorrect configuration in the ROM
5: Fatal fault
6: At least one I/O connection is active
7: All I/O connections in the quiescent state
2
Assembly Object, Instance Number: 4 hex
Get Attribute single
Get Attribute single
Set Attribute single
Table 6- 33 Class Attribute
Table 6- 34 Instance Attribute
3 get Array of
Assembly 1 byte array