Appendix
A.2 Parameter macros
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
593
Sink
Source
Parameters
Description
DO
Parameters
Description
DO
p4076[1]
Type of analog outputs
TM31
1
Voltage 0...10 V
TM31
p4071[0]
Signal analog output 0
TM31
r0063
Actual speed value smoothed
Vector
p4071[1] Signal analog output 1 TM31 r0068 Absolute current actual value Vector
p4100
Type of temperature sensor
TM31
0
Evaluation disabled
TM31
p4102[0] Alarm threshold, temperature sens-
ing
TM31 251 °C When this value is exceeded,
alarm A35211 is triggered.
TM31
p4102[1] Fault threshold for temperature
sensing
TM31 251 °C When this value is exceeded,
fault F35207 is triggered.
TM31
p7003
Winding system
Vector
1
Separate winding systems
Vector
Parameter macro p0700 = 1: PROFIdrive (70001)
This macro is used to set the PROFIdrive interface as the default command source.
Table A- 2 Parameter macro p0700 = 1: PROFIdrive
Sink
Source
Parameter
Description
DO
Parameter
Description
DO
p0840[0]
ON/OFF1
Vector
r2090.0
PZD 1 bit 0
Vector
p0844[0]
No OFF2_1
Vector
r2090.1
PZD 1 bit 1
Vector
p0845[0]
No OFF2_2
Vector
r0722.4
CU DI4
CU
p0848[0]
No OFF3_1
Vector
r2090.2
PZD 1 bit 2
Vector
p0849[0]
No OFF3_2
Vector
r0722.5
CU DI5
CU
p0806
Inhibit LOCAL mode
Vector
0
Vector
p0810
Changeover CDS bit 0
Vector
0
Vector
p0852
Enable operation
Vector
r2090.3
PZD 1 bit 3
Vector
p0854
Control request
Vector
r2090.10
PZD 1 bit 10
Vector
p0922
Profibus PZD telegram selection
Vector
999
Free telegram configuration
p1020
FSW bit 0
Vector
0
Vector
p1021
FSW bit 1
Vector
0
Vector
p1035
MOP raise
Vector
r2090.13
PZD 1 bit 13
Vector
p1036 MOP lower Vector r2090.14 PZD 1 bit 14 Vector
p1113
Direction reversal
Vector
r2090.11
PZD 1 bit 11
Vector
p1140 Enable RFG Vector r2090.4 PZD 1 bit 4 Vector
p1141
Start RFG
Vector
r2090.5
PZD 1 bit 5
Vector
p1142
Enable nsetp
Vector
r2090.6
PZD 1 bit 6
Vector
p2103
Acknowledge fault 1
Vector
r2090.7
PZD 1 bit 7
Vector
p2104
Acknowledge fault 2
Vector
r0722.3
CU DI3
CU
p2106
Ext. fault_1
Vector
r0722.6
CU DI6
CU
p2107
Ext. fault_2
Vector
1
Vector
p2112
Ext. alarm_1
Vector
r0722.11
CU DI11
CU
p2116
Ext. alarm_2
Vector
1
Vector

Table of Contents