[ueb-ansprechwertumsch-020926-rei, 1, en_GB]
Figure 2-84
Dynamic Cold Load Pickup Timing Sequence
During power up of the protective relay with an open circuit breaker, the time delay CB Open Time is
started, and is processed using the “normal” settings. Therefore, when the circuit breaker is closed, the
“normal” settings are effective.
Functions
2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection
SIPROTEC 4, 7UT6x, Manual 173
C53000-G1176-C230-5, Edition 09.2016