Protocol-dependent Functions
Protocol → IEC
60870-5-10
3
IEC 61850
Ethernet
(EN100)
PROFIBUS
FMS
PROFIBUS DP DNP3.0 Modbus
ASCII/RTU
Additional
Service inter-
face
(optional)
Function ↓
Operational
Measured values
Yes (feste
Werte)
Yes Yes Yes Yes Yes Yes
Metered Values Yes Yes Yes Yes Yes Yes Yes
Fault Recording Yes Yes Yes No
only via
additional
service inter-
face
No
only via
additional
service inter-
face
No
only via
additional
service inter-
face
Yes
Remote relay
setting
No
only via
additional
interface
No
only via
additional inter-
face
Yes No
only via
additional
service inter-
face
No
only via
additional
service inter-
face
No
only via
additional
service inter-
face
Yes
User-defined
annunciations
and switching
objects
Yes Yes Yes User-defined
annuncia-
tions in CFC
User-defined
annuncia-
tions in CFC
User-defined
annuncia-
tions in CFC
Yes
Time synchroni-
sation
via
protocol;
DCF77/
IRIG B;
Interface;
Binary input
via
protocol (NTP);
DCF77/IRIG B;
Interface;
Binary input
via
protocol;
DCF77/
IRIG B; Inter-
face;
Binary input
via
protocol;
DCF77/
IRIG B;
Interface;
Binary input
via
protocol;
DCF77/
IRIG B;
Interface;
Binary input
via
DCF77/
IRIG B;
Interface;
Binary input
-
Annunciations
with time stamp
Yes Yes Yes Yes Yes No Yes
Commissioning tools
Indication meas-
ured value
blocking
Yes Yes Yes No No No Yes
Generation of
test annuncia-
tions (DIGSI)
Yes Yes Yes No No No Yes
Physical properties
Mode asynchro-
nousous
Synchronous asynchro-
nousous
asynchro-
nous
asynchro-
nous
asynchro-
nous
-
Transmission
mode
Cyclical/
event
Cyclical/event Cyclical/
event
Cyclical Cyclical/
event
Cyclical -
Baud rate 4800 to
38400
up to
100 MBaud
up to
1.5 MBaud
up to
1.5 MBaud
2400 to
19200
2400 to
19200
2400 to
38400
Connection to
device
Electrical:
RS232
RS485
optical:
ST connector
Ethernet TP Electrical:
RS485
optical:
ST connector
(single or
double ring)
Electrical:
RS485
optical:
ST connector
(double ring)
Electrical:
RS485
optical:
ST connector
Electrical:
RS485
optical:
ST connector
Electrical:
RS232
RS485
optical.
ST connector
RTD-box 7XV5662-xAD Yes
E.7
Default Settings and Protocol-dependent Functions
E.7 Protocol-dependent Functions
SIPROTEC 4, 7UT6x, Manual 537
C53000-G1176-C230-5, Edition 09.2016

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 7UT6 Series and is the answer not in the manual?

Siemens SIPROTEC 4 7UT6 Series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4 7UT6 Series
CategoryProtection Device
LanguageEnglish