EasyManua.ls Logo

Siemens SIPROTEC 4 7UT6 Series - Thermal Overload Protection

Siemens SIPROTEC 4 7UT6 Series
684 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Thermal Overload Protection
Setting Ranges
Factor k according to IEC 60255-8 0.10 to 4.00 Increments 0.01
Time constant τ 1.0 min to 999.9 min Increments
0.1 min
Cooling down factor at motor
standstill
K
τ
-Faktor 1.0 to 10.0 Increments 0.1
Thermal alarm stage Θ
Alarm
Trip
50 % to 100 % referred
to trip temperature rise
Increments 1 %
Current alarm stage
Ι
Alarm
0.10 to 4.00 A
1)
Increments 0.01 A
Start-up recognition
Ι
motor startup
0.60 to 10.00 A
1)
or ∞ (no start-up recog-
nition)
Increments 0.01 A
Emergency start run-on time T
Run-on
10 s to 15000 s Increments 1 s
1)
Secondary values based on Ι
N
= 1 A; for Ι
N
= 5 A the currents must be multiplied by 5.
Trip Characteristic
Formula for primary values:
Trip Characteristic curve for Ι / (k ⋅ Ι
N
) ≤8
with
t Trip time in minutes
τ
th
Heating-up time constant
Ιn
Actual load current
Ι
vor
Preload current
k Setting factor per IEC 60255-8
Ι
N
Nominal current for the protected object
Dropout to Pickup Ratios
Θ/Θ
Aus
Dropout with Θ
Alarm
Θ/Θ
Alarm
approx. 0.99
Ι/Ι
Alarm
approx. 0.97
Tolerances
For one 3-phase measuring location
relating to k · Ι
N
3 %, or 10 mA
1)
;
Klasse 3% according to IEC 60255-8
Referring to tripping time 3 % or 1.2 s at f
N
= 50/60 Hz
5 % or 1.2 s at f
N
= 16.7 Hz (only 7UT613/63x)
for Ι/(k·Ι
N
) > 1.25
1)
Secondary values based on Ι
N
= 1 A; for Ι
N
= 5 A the currents must be multiplied by 5.
4.9
Technical Data
4.9 Thermal Overload Protection
440 SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016

Table of Contents

Related product manuals