Characteristics
General Features
Powerful 32-bit microprocessor system
Complete digital measured value processing and control, from the sampling and digitalization of the
analogue input quantities to the initiation of outputs for tripping or closing circuit breakers
Complete galvanic and reliable separation between the internal processing circuits of the device and the
external measurement, control, and power supply circuits because of the design of the analog input
transducers, binary input and output modules, and the DC/DC or AC/DC converters
Suitable for power transformers, generator, motors, reactors, or smaller busbar arrangements, as well as
for multi-terminal lines and multi-winding transformers
Easy device operation through an integrated operator panel or by means of a connected personal
computer running DIGSI.
Transformer Differential Protection
Current restraint tripping characteristic
Restraint feature against high inrush currents with 2nd harmonic
Restraint feature against high inrush currents with Current waveform analysis CWA
Restraint feature against transient and steady-state fault currents caused e.g. by overexcitation of trans-
formers, using a further harmonic (3rd or 5th harmonic)
Insensitivity to DC components and current transformer saturation
High level of stability even with different degrees of current transformer saturation
High-speed instantaneous trip in case of high-current transformer faults
Independent of the conditioning of the starpoint(s) of the power transformer
Adjustable to the conditioning of the starpoint(s) of the power transformer
Increased earth-fault sensitivity during detection of the ground current of an earthed transformer
winding
Integrated matching of the transformer connection group
Integrated matching of the transformation ratio including different rated currents of the transformer
windings.
Differential Protection for Generators and Motors
Current restraint tripping characteristic
High sensitivity
Short tripping time
Insensitivity to DC components and current transformer saturation
High level of stability even with different degrees of current transformer saturation
Independent of the conditioning of the starpoint
Differential Protection for Mini-Busbars and Short Lines
Tripping characteristic with current restraint
Short tripping time
Insensitivity to DC components and current transformer saturation
1.3
Introduction
1.3 Characteristics
SIPROTEC 4, 7UT6x, Manual 21
C53000-G1176-C230-5, Edition 09.2016