High level of stability even with different degrees of current transformer saturation
•
Monitoring of the current connections with operation currents
Busbar Protection
•
Single-phase differential protection for a busbar with up to 7 or 9 or 12 feeders (depending on the
variant ordered)
•
Either one relay per phase or one relay connected via interposed summation current transformers
•
Tripping characteristic with current restraint
•
Short tripping time
•
Insensitivity to DC components and current transformer saturation
•
High level of stability even with different degrees of current transformer saturation
•
Monitoring of the current connections with operation currents.
Earth Fault Differential Protection
•
Earth fault protection for earthed transformer windings, generators, motors, shunt reactors, or starpoint
formers
•
Short command duration
•
High sensitivity for earth faults within the protected zone
•
High stability against external earth faults using the magnitude and phase relationship of through-
flowing earth current
•
2 restricted earth fault protection functions possible (only 7UT613/63x)
High-impedance Differential Protection
•
Highly sensitive fault current detection using a common (external) burden resistor
•
Short tripping time
•
Insensitive against DC components and current transformer saturation
•
High stability with optimum matching
•
Suitable for earth fault detection on earthed generators, motors, shunt reactors, and transformers,
including auto-transformers, with or without earthed starpoint
•
Suitable for any voltage measurement (via the resistor current) for application of high-impedance unit
protection
Tank Leakage Protection
•
For transformers or reactors the tank of which is installed isolated or with high resistance
•
Monitoring of the current flowing between the tank and ground
•
Can be connected via a „normal“ current input of the device or the special highly sensitive current input
(3 mA smallest setting)
Earth Fault Differential Protection
•
Earth fault protection for earthed transformer windings, generators, motors, shunt reactors, or starpoint
formers
•
Short command duration
•
High sensitivity for earth faults within the protected zone
Introduction
1.3 Characteristics
22 SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 7UT6 Series and is the answer not in the manual?

Siemens SIPROTEC 4 7UT6 Series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4 7UT6 Series
CategoryProtection Device
LanguageEnglish

Related product manuals