High stability against external earth faults using the magnitude and phase relationship of through-
flowing earth current
2 restricted earth fault protection functions possible (only 7UT613/63x)
Time Overcurrent Protection for Earth Current
Two definite time delayed overcurrent stages for the earth current, e.g. current between starpoint and
earth
Additionally, one inverse time delayed overcurrent stage for the earth current
Selection of various inverse time characteristics of different standards is possible, alternatively a user
defined characteristic can be specified
The 3 stages can be combined as desired
External blocking facility for any desired stage (e.g. for reverse interlocking)
Instantaneous trip when switching on a dead fault with any desired stage
Inrush restraint function with 2nd harmonic
Dynamic switchover of the time overcurrent parameters, e.g. during cold-loaded start-up of the power
plant
2 time overcurrent protection functions for earth current possible (only 7UT613/63x)
1-phase Overcurrent Protection
Two definite time delayed overcurrent stages which can be combined as desired
For any 1-phase overcurrent detection
Can be assigned to the “normal” 1-phase current input or to the highly sensitive current input
Suitable for detection of very small current (e.g. for high-impedance unit protection or tank leakage
protection)
Suitable for detection of any desired AC voltage using an external series resistor (e.g. for high-impedance
unit protection)
External blocking facility for any stage
Unbalanced Load Protection
Evaluation of the negative sequence system of the three phase currents of any desired side of the
protected object or any three-phase measuring point
Two definite time delayed negative sequence current stages and one additional inverse time delayed
negative sequence current stage
Selection of various inverse time characteristics of different standards is possible, alternatively a user
defined characteristic can be specified
The stages can be combined as desired
Trip blocking on detection of broken wire
Thermal characteristic with adjustable negative sequence factor and adjustable cooldown time
Thermal Overload Protection
Thermal replica of current-initiated heat losses
True RMS current calculation
Can be assigned to any desired side of the protective object
Adjustable thermal warning stage
Adjustable current warning stage
Introduction
1.3 Characteristics
SIPROTEC 4, 7UT6x, Manual 23
C53000-G1176-C230-5, Edition 09.2016

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 7UT6 Series and is the answer not in the manual?

Siemens SIPROTEC 4 7UT6 Series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4 7UT6 Series
CategoryProtection Device
LanguageEnglish

Related product manuals