EasyManua.ls Logo

Siemens SIPROTEC 4 7UT6 Series - Unbalanced Load Protection

Siemens SIPROTEC 4 7UT6 Series
684 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Unbalanced Load Protection
Characteristics
Definite-time stages DT
Ι
2
>>, Ι
2
>
Inverse time stages
(acc. to IEC or ANSI)
IT
Ι
2P
One of the characteristics shown in
Figure 4-14 to Figure 4-17 can be selected
Reset characteristics
with disk emulation
IT For illustrations of possible reset time charac-
teristics see Figure 4-14 to Figure 4-17 on
the left-hand side.
Operating Range
0.1 to 4 Ι/ΙnS
Current Stages
High current stage
Ι
2
>>
0.10 A to 3.00 A
1)
Increments 0.01 A
T
Ι2
>> 0.00 s to 60.00 s
or ∞ (no trip)
Increments 0.01 s
Definite time current element
(50Ns- 2, 50Ns-1)
Ι
2
>
0.10 A to 3.00 A
1)
Increments 0.01 A
T
Ι2
> 0.00 s to 60.00 s
or ∞ (no trip)
Increments 0.01 s
Inverse current element (51Ns-
IEC)
Ι
2P
0.10 A to 2.00 A
1)
Increments 0.01 A
T
Ι2P
0.05 s to 3.20 s
or ∞ (no trip)
Increments 0.01 s
Inverse current element (51Ns-
ANSI)
Ι
2P
0.10 A to 2.00 A
1)
Increments 0.01 A
D
Ι2P
0.50 s to 15.00 s
or ∞ (no trip)
Increments 0.01 s
Tolerances with inverse time
2)
Currents 3 % of setting value or 1 % nominal current
Times 1 % of setting value or 10 ms
Tolerances with definite time (IEC)
2)
Currents Pickup at
1.05 ≤ Ι
2
/Ι
2P
≤ 1.15
Times 5 % ± 15 ms
5 % ± 45 ms
at f
N
= 50/60 Hz
at f
N
= 16.7 Hz
(only 7UT613/63x)
for 2 ≤ Ι
2
/Ι
2P
≤ 20
and T
Ι2P
/s ≥ 1
Tolerances with definite time (ANSI)
2)
Times 5 % ± 15 ms
5 % ± 45 ms
bei f
N
= 50/60 Hz
bei f
N
= 16.7 Hz
(only 7UT613/63x)
for 2 ≤ Ι
2
/Ι
2P
≤ 20
and D
Ι2P
/s ≥ 1
The set times are pure delay times.
1)
Secondary values for Ι
N
= 1 A; bei Ι
N
= 5 A the currents must be multiplied by 5.
2)
For one 3-phase measuring location
4.8
Technical Data
4.8 Unbalanced Load Protection
432 SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016

Table of Contents

Related product manuals